dc.description.abstractLa presente tesis de investigación, evalúa el nivel de desempeño sísmico del pabellón B1 del Hospital de Alta Complejidad “Virgen de la Puerta”, que fue diseñada bajo los lineamientos normativos sismorresistentes del año 2003, el cual con el transcurrir de los años, se ha ido mejorando e implementando con nuevos parámetros que nos permite conocer nuestras limitaciones al momento de diseñar infraestructuras de uso esenciales, importantes, comunes y temporales como lo describe la norma E – 030, 2018. Al ser el hospital en mención considerada de uso esencial; por su capacidad de operatividad y funcionalidad; se encuentra ubicado en una zona de alto nivel sísmico y ante la posibilidad de ocurrencia de sismo de mediana o gran escala, es necesario conocer su desempeño, para lo cual existen varias herramientas tales como Pushover, Análisis Paso a Paso, Análisis Dinámico Incremental, entre otras. Siendo necesario analizar la edificación; por ser de gran importancia; mediante un Análisis Dinámico Incremental. Un análisis por desempeño evalúa la edificación en base a las propiedades de los elementos estructurales mediante modelos teóricos del comportamiento de los materiales tales como Mander, Takeda y modelos histerético que han sido obtenidos mediante ensayos, los cuales permiten tener resultados más confiables que un diseño normativo. El análisis IDA considera la no linealidad de los materiales (Concreto y Acero), y somete la estructura a registros sísmicos reales, siendo estos escalados a diferentes niveles de aceleraciones del suelo (PGA); para luego conocer si cuenta con los niveles de aceptación que rigen el código del FEMA 356 para infraestructuras de uso esencial donde detalla que éstas deberán permanecer en ocupación inmediata. Por otro lado, según la filosofía de diseño sismorresistente, espera que la estructura no sobrepase derivas máximas de 0.007, siendo este valor muy genérico. Se estima que los elementos estructurales de la edificación hospitalaria, satisfarán los requerimientos del nivel de Ocupación Inmediata cuando sea sometida al sismo máximo esperado con un PGA de 0.675g para un periodo de retorno Tr = 2475 años, garantizando su continua funcionalidad. Nuestra evaluación es solo para elementos estructurales, aunque habrá pocos elementos que presenten rotulación en algunos puntos generando que los equipos médicos salgan de su posición o pierdan precisión, no permitiendo una ocupación inmediata, aunque la estructura está casi en el rango.es_PE
dc.description.abstractThis research thesis evaluates the level of seismic performance of Hall B1 of the High Complexity Hospital “Virgen de la Puerta”, which was designed under the seismic-resistant normative guidelines of 2003, which over the years, has been It has been improving and implementing with new parameters that allow us to know our limitations when designing essential, important, common and temporary use infrastructures as described in the standard E - 030, 2018. As the present hospital is considered essential use; for its operability and functionality; It is located in an area of high seismic level and in the face of the possibility of occurrence of medium or large scale earthquake, it is necessary to know its performance, for which there are several tools such as Pushover, Step by Step Analysis, Incremental Dynamic Analysis, among others. It is necessary to analyze the building through an Incremental Dynamic Analysis, for being a structure of great importance. A performance analysis evaluates the building based on the properties of the structural elements through theoretical models of the behavior of materials such as Mander, Takeda and hysteretic models that have been obtained through tests, which enable more reliable results than a normative design. The IDA analysis considers the non-linearity of the materials (Concrete and Steel), and submits the structure to real seismic registers, these being scaled to different levels of soil accelerations (PGA); and then know if it has the levels of acceptance that govern the code of FEMA 356 for essential use infrastructures where it details that they must remain in immediate occupation. On the other hand, according to the seismic-resistant design philosophy, it expects that the structure does not exceed maximum drifts of 0.007, this value being very generic. It is estimated that the structural elements of the hospital building will satisfy the requirements of the Immediate Occupancy level when submitted to the maximum expected earthquake with a PGA of 0.675g for a return period Tr = 2475 years, guaranteeing its continuous functionality. Our evaluation is only for structural elements, although there will be few elements that present signage at some points causing medical teams to leave their position or lose precision, not allowing immediate occupation, although the structure is almost in range.en_US
dc.description.uriTesises_PE
dc.formatapplication/pdfes_PE
dc.language.isospaes_PE
dc.publisherUniversidad Privada Antenor Orregoes_PE
dc.relation.ispartofseriesT_ING.CIVIL_1771
dc.rightsinfo:eu-repo/semantics/closedAccesses_PE
dc.rights.urihttps://creativecommons.org/licenses/by/4.0/es_PE
dc.sourceUniversidad Privada Antenor Orregoes_PE
dc.sourceRepositorio Institucional - UPAOes_PE
dc.subjectSísmicoes_PE
dc.subjectIncrementales_PE
dc.titleDeterminación del nivel de desempeño sísmico del Hospital de Alta Complejidad Virgen de la Puerta - La Esperanza pabellón B1, utilizando el análisis dinámico incrementales_PE
dc.typeinfo:eu-repo/semantics/bachelorThesises_PE
thesis.degree.levelTítulo Profesionales_PE
thesis.degree.grantorUniversidad Privada Antenor Orrego. Facultad de Ingenieríaes_PE
thesis.degree.nameIngeniero Civiles_PE
thesis.degree.disciplineIngeniería Civiles_PE
dc.subject.ocdehttps://purl.org/pe-repo/ocde/ford#2.01.00
renati.typehttps://purl.org/pe-repo/renati/type#tesis
renati.levelhttps://purl.org/pe-repo/renati/level#tituloProfesional
dc.publisher.countryPEes_PE


Ficheros en el ítem

Thumbnail

Este ítem aparece en la(s) siguiente(s) colección(es)

Mostrar el registro sencillo del ítem

info:eu-repo/semantics/closedAccess
Excepto si se señala otra cosa, la licencia del ítem se describe como info:eu-repo/semantics/closedAccess